I have a 330a two stop that has been off for about a month. It Was running fine previously. Went into the machine room to do an annual test and foud no screen reed out; found the 24v logic voltage supply was no good and changed. Now I have a reed out of 'BLOCK READY 0=01 1ii unv'. Attemted to reset many times to no avail.

Schindler 330a Manual

Guide

Can not even run on inspection. Does any one know what could be wrong? Much appreciated. 09/19/12 12:01 AM Re: schindler 330a Joined: Mar 2012 Posts: 96 journeyman journeyman Joined: Mar 2012 Posts: 96. Well,don't think there is a battery backup, RAM board will hold parameters, agree try' jumping pressure sw. Sad to say its a Schindler, you never know.

Unv means unavailable. Did you do a reboot? Press button on the board that is mounted to the Main relay board 3times in 1sec. Intervals,then when screen shows system boot, press and hold for 5 sec. This will reboot entire system. Sometimes you have to put controller on MR inspection.

330a

This clears most errors. 10/08/12 12:35 AM Re: schindler 330a Joined: May 2012 Posts: 186 member member Joined: May 2012 Posts: 186.

Schindler 330a Repair Manual

Contents Overview The Schindler 300A model is Schindler's former hydraulic model in the U.S and Canada. The Schindler 300A comes in Inground and Hole-less models. The 300A holeless models would have two pistons on the sides of the elevator where the doors do NOT open. Specs. Inground or holeless hydraulic. RT or MT fixtures. Serves up to 8 floors.