An existing Westinghouse IQ-1000 II motor protection relay does not have a Core-Balance CT, however its Ground Fault trip element is enabled and set. The manual states that ground fault detection requires an 'optional ground fault (zero sequence) transformer be installed'. If only 3 phase CTs are installed, does the relay determine the ground fault current from the residual current of the three phase CTs? Or will the relay ignore the ground fault setting because there is no core-balance CT connected? RE: Westinghouse IQ-1000 II Ground Fault Protection - CBCT Required? (Electrical) 17 Aug 11 08:11. It's only 'optional' in the sense that you don't have to have earth fault protection.

If you want earth fault protection then the 50:5 CT is not optional. The E/F CT is expected to have a 50:5 ratio and this can't be configured internally to a different value. If your line CTs happen to match this ratio then you could probably use the earth fault input with the residual connection. I suppose you 'could' use it with a different line CT ratio, but the scaling would be off and possibly not sensitive enough if you have large ratio CTs. If we learn from our mistakes I'm getting a great education! RE: Westinghouse IQ-1000 II Ground Fault Protection - CBCT Required? Actually there are two kinds of Ground Fault; Residual and Zero Sequence.

If all you need is Residual, the relay will take car of that internally by summing the existing current signals, meaning you don't need an external Zero Sequence (core balanced) CT. Unless you have a resistance grounded system, Residual, aka Arcing Ground Fault, most people don't add the ZSCT on a motor. 'Dear future generations: Please accept our apologies. We were rolling drunk on petroleum.'

— Kilgore Trout (via Kurt Vonnegut) For the best use of Eng-Tips, please click here - RE: Westinghouse IQ-1000 II Ground Fault Protection - CBCT Required? (Electrical) 21 Aug 11 02:05. Jraef, The relay isn't really designed to accommodate a residual connection. If it were then the CT ratio would be configurable. It is intended only for a ZSCT. I wouldn't have thought it was a big deal to allow the earth fault CT ratio to be adjustable, but who knows what the designer had in mind - probably making the customer buy a matching CT!

Manual

- If we learn from our mistakes I'm getting a great education! RE: Westinghouse IQ-1000 II Ground Fault Protection - CBCT Required? (Electrical) 21 Aug 11 11:02.

Now you can build your own list of parts, that will email a copy to us and yourself. We’ll tally up a quote and email it back to you. Here is how:. Navigate or use the “General Search” box to locate the part(s) you are looking for. Click the “Quote” button to the right of any parts you would like to receive a quote for. Notice the box in the top right corner of the page which show the total number of parts that you would like quoted.

Click the “Quote” button on the top right of the page to view your list of parts. Increase or decrease the quantity or click the red “minus” button to remove an item from the list. Once satisfied with your list, fill out your name and email address and click the “Request Quote” button. Finally check your email. Citroen picasso 2018 manual. You should receive an email with your list of items. Monster Controls will respond as soon as they can with your quote.

Westinghouse Iq 1000 Ii Manual

You are also welcome to call us at 888-820-4335.

latinnowbot – 2020